| Parameter | Nilai |
|---|---|
| GTIN | 4046356163675 |
| Kunci Pesanan | 2920450 |
| Halaman katalog | Page 41 (C-6-2015) |
| Unit pembungkusan | 1 pc |
| Nota (Umum) | Usable in all low-voltage systems between L-N or L-PEN.Only usable in IT Systems between L-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation. (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE= RAaccordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a) |
| Negara asal | DE (Germany) |
| (Data sambungan) | L-G |
| Nombor tarif tersuai | 85363030 |
| (Keadaan ambien) | PBT |
| (Litar pelindung) | 4.5 Nm (25 mm² ... 35 mm²) |
| (Data sambungan UL) | EN 61643-11 2012 |
| Altitud (Dimensi) | ≤ 2000 m (amsl (above mean sea level)) |
| Jenis (Keadaan ambien) | DIN rail module, two-section, divisible |
| (Penerangan tambahan) | 762 V AC (120 min / withstand mode) |
| Warna (Keadaan ambien) | jet black RAL 9005 |
| Jenis SPD (Data Sambungan) | 4CA |
| Kedalaman (Data Komersial Utama) | 65.7 mm (incl. DIN rail 7.5 mm) |
| Lebar (Data Komersial Utama) | 53.4 mm |
| (Piawaian dan Peraturan) | No hazardous substances above threshold values |
| Jenis EN (Keadaan ambien) | T2 |
| Ketinggian (Data Komersial Utama) | 89.8 mm |
| Voltan nominal (Data sambungan) | 400/690 V AC |
| Kejutan (operasi) (Dimensi) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Tahap perlindungan (Dimensi) | IP20 (only when all terminal points are used) |
| Benang skru (Litar pelindung) | M5 |
| Jenis pemasangan (Keadaan ambien) | DIN rail: 35 mm |
| Getaran (operasi) (Dimensi) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
| Frekuensi nominal (Data sambungan) | 50/60 Hz |
| Mod perlindungan (Data sambungan) | L-L |
| Berat setiap Keping (tidak termasuk pembungkusan) | 398.200 g |
| Bahan perumahan (Keadaan ambien) | PA 6.6 |
| Panjang pelucutan (Litar pelindung) | 16 mm |
| Tork pengetatan (spesifikasi UL) | 30 lbf-in. |
| RoHS (Piawaian dan Peraturan) China | Environmentally friendly use period: unlimited = EFUP-e |
| Kaedah sambungan (Litar pelindung) | Fork-type cable lug |
| Padang mendatar (Data Komersial Utama) | 3 Div. |
| Tork pengetatan (Litar pelindung) | 3 Nm (1,5 mm² ... 16 mm²) |
| Cara perlindungan (Keadaan ambien) | L-PE |
| Tahap pencemaran (Keadaan ambien) | 2 |
| Bilangan kedudukan (Keadaan ambien) | 3 |
| Masa tindak balas tA (Penerangan tambahan) | ≤ 25 ns |
| Piawaian/peraturan (data sambungan UL) | IEC 61643-11 2011 |
| Sistem pengagihan kuasa (Data sambungan) | Delta |
| Suhu ambien (operasi) (Dimensi) | -40 °C ... 80 °C |
| Sistem bekalan kuasa IEC (Keadaan ambien) | TN-C |
| Pengelasan ujian IEC (Keadaan ambien) | II |
| Voltan nominal UN (Penerangan tambahan) | 400/690 V AC (TN-C) |
| Tingkah laku TOV di UT (Penerangan tambahan) | 690 V AC (5 s / withstand mode) |
| Kelembapan yang dibenarkan (operasi) (Dimensi) | 5 % ... 95 % |
| Frekuensi nominal fN (Penerangan tambahan) | 50 Hz (60 Hz) |
| IPE arus baki (Penerangan tambahan) | ≤ 0.75 mA |
| Keratan rentas konduktor AWG (spesifikasi UL) | 10 ... 2 |
| Arus beban dinilai IL (Penerangan tambahan) | 80 A |
| Voltan baki Ures (Penerangan tambahan) | ≤ 2.5 kV (at In) |
| Keratan rentas konduktor AWG (Litar pelindung) | 15 ... 2 |
| Pepejal keratan rentas konduktor (Litar pelindung) | 1.5 mm² ... 35 mm² |
| Arus nyahcas nominal In(LG) (Data sambungan) | 10 kA |
| Arus nyahcas nominal In(LL) (Data sambungan) | 10 kA |
| Mesej kerosakan perlindungan lonjakan (Keadaan ambien) | optical |
| Suhu ambien (penyimpanan/pengangkutan) (Dimensi) | -40 °C ... 80 °C |
| Keratan rentas konduktor fleksibel (Litar pelindung) | 1.5 mm² ... 16 mm² |
| Voltan pengehad yang diukur MLV (LG) (Data sambungan) | 2310 V |
| Voltan pengehad yang diukur MLV (LL) (Data sambungan) | 4270 V |
| Tahap perlindungan voltan Naik (Penerangan tambahan) | ≤ 2.5 kV |
| Penggunaan kuasa siap sedia PC (Penerangan tambahan) | ≤ 450 mVA |
| Voltan berterusan maksimum UC (Penerangan tambahan) | 580 V AC |
| Penarafan mudah terbakar mengikut UL 94 (Keadaan ambien) | V-0 |
| Penarafan arus litar pintas ISCCR (Penerangan tambahan) | 25 kA |
| Jarak antara bahagian hidup dan bahagian yang dibumikan (Keadaan ambien) | 5 mm |
| Fius sandaran maksimum dengan pendawaian cabang (Penerangan tambahan) | 125 A (gG) |
| Arus nyahcas nominal In(8/20) µs (Penerangan tambahan) | 15 kA |
| Voltan operasi berterusan maksimum MCOV (LG) (Data sambungan) | 580 V AC |
| Voltan operasi berterusan maksimum MCOV (LL) (Data sambungan) | 1160 V AC |
| Arus nyahcas maksimum Imax(8/20) µs (Penerangan tambahan) | 30 kA |
| Fius sandaran maksimum dengan pendawaian melalui jenis-V (Penerangan tambahan) | 80 A (gG) |
Spesifikasi teknikal dan data prestasi
Panduan pemasangan dan operasi