| Parameter | Nilai |
|---|---|
| GTIN | 4055626456652 |
| Kunci Pesanan | 2910105 |
| (Umum) | IEC 61010-2-201 |
| (Lukisan) | |
| (Data EMC) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| (Piawaian) | 2 kV (Test Level 3 - asymmetrical) |
| Halaman katalog | Page 268 (C-4-2019) |
| Unit pembungkusan | 1 pc |
| Kedalaman (Lukisan) | 125 mm |
| Lebar (Lukisan) | 59 mm |
| Negara asal | TH (Thailand) |
| ETIM 5.0 (eCl@ss) | EC002540 |
| ETIM 6.0 (eCl@ss) | EC002540 |
| ETIM 7.0 (eCl@ss) | EC002540 |
| Ketinggian (Lukisan) | 130 mm |
| Input (Piawaian) | 2 kV (Test Level 3 - symmetrical) |
| Gambarajah (Lukisan) | |
| Output (Piawaian) | 1 kV (Test Level 2 - symmetrical) |
| Voltan (Piawaian) | 230 V AC |
| Komen (Piawaian) | Criterion B |
| Nombor tarif tersuai | 85044030 |
| (Keadaan ambien) | 2.4 kV AC (routine test) |
| RoHS China (data EMC) | Environmentally Friendly Use Period = 25; |
| Kekerapan (Piawaian) | 50 Hz |
| REACh SVHC (data EMC) | Lead 7439-92-1 |
| Kriteria A (Piawaian) | Normal operating behavior within the specified limits. |
| Kriteria B (Piawaian) | Temporary impairment to operational behavior that is corrected by the device itself. |
| Penurunan voltan (Standard) | EN 61000-4-11 |
| Gambarajah blok (Lukisan) | |
| Pelepasan hingar (Piawaian) | EN 55016 |
| Teks tambahan (Piawaian) | Test Level 2 |
| Kelas iklim (Dimensi) | 3K3 (in acc. with EN 60721) |
| Julat frekuensi (Piawaian) | 0.15 MHz ... 80 MHz |
| Pelepasan di udara (Piawaian) | 8 kV (Test Level 3) |
| eCl@ss 8.0 (Pengelasan) | 27049002 |
| eCl@ss 9.0 (Pengelasan) | 27040701 |
| Pelepasan sentuhan (Piawaian) | 6 kV (Test Level 3) |
| Arus harmonik (Piawaian) | EN 61000-3-2 |
| Bilangan tempoh (Piawaian) | 1 period |
| eCl@ss 11.0 (Pengelasan) | 27040701 |
| Lukisan dimensi (Lukisan) | |
| Penamaan piawai (Umum) | Requirement of the semiconductor industry with regard to mains voltage dips |
| Kecekapan (Keadaan ambien) | typ. 93 % (120 V AC) |
| Berat bersih (Keadaan ambien) | 1 kg |
| Piawaian/peraturan (Umum) | SEMI F47 - 0706 (185 V AC) |
| Kekuatan medan ujian (Piawaian) | 10 V/m (Test Level 3) |
| eCl@ss 10.0.1 (Pengelasan) | 27040701 |
| Tahap pencemaran (Dimensi) | 2 |
| Ketinggian pemasangan (Dimensi) | ≤ 3000 m (> 2000 m, Derating: 10 %/1000 m) |
| Tahap perlindungan (Dimensi) | IP20 |
| Arahan Voltan Rendah (Piawaian) | Conformance with Low Voltage Directive 2014/35/EC |
| Gangguan yang dijalankan (Piawaian) | EN 61000-4-6 |
| Nyahcas elektrostatik (Piawaian) | EN 61000-4-2 |
| Transien pantas (letusan) (Standard) | EN 61000-4-4 |
| Pelepasan hingar yang dialirkan (Piawaian) | EN 55016 |
| Medan HF Elektromagnet (Piawaian) | EN 61000-4-3 |
| Berat setiap Keping (tidak termasuk pembungkusan) | 1,240.000 g |
| Bahan perumahan (Keadaan ambien) | Aluminum (AlMg3) / sheet steel, zinc-plated |
| Kelas perlindungan (Keadaan ambien) | I |
| Kedudukan pemasangan (Keadaan ambien) | horizontal DIN rail NS 35, EN 60715 |
| Beban voltan lonjakan (lonjakan) (Piawaian) | EN 61000-4-5 |
| Bahan selak kaki (Keadaan ambien) | Sheet steel, zinc-plated |
| Tahap perlindungan (Keadaan ambien) | IP20 |
| Keserasian elektromagnet (Piawaian) | Conformance with EMC Directive 2014/30/EU |
| Arahan pemasangan (Keadaan ambien) | alignable: 0 mm horizontally, 30 mm vertically |
| Suhu ambien (operasi) (Dimensi) | -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K) |
| Keperluan EMC untuk imuniti hingar (Umum) | EN 61000-6-2 |
| MTBF (IEC 61709, SN 29500) (Keadaan ambien) | > 900000 h (25 °C) |
| Input voltan penebat / PE (Keadaan ambien) | 3.5 kV AC (type test) |
| Penarafan mudah terbakar mengikut UL 94 (Dimensi) | V0 () |
| Suhu ambien (penyimpanan/pengangkutan) (Dimensi) | -40 °C ... 85 °C |
| Input/output voltan penebat (Keadaan ambien) | 4 kV AC (type test) |
| Suhu ambien (jenis permulaan diuji) (Dimensi) | -40 °C |
| Arahan perlindungan alam sekitar (Keadaan ambien) | RoHS Directive 2011/65/EU |
| Kelembapan relatif maksimum yang dibenarkan (operasi) (Dimensi) | ≤ 95 % (at 25 °C, non-condensing) |
| Jarak pemasangan kanan/kiri (aktif, pasif) (Lukisan) | 0 mm / 0 mm (POut≥50% ) |
| Jarak pemasangan atas/bawah (aktif, pasif) (Lukisan) | 30 mm / 30 mm (POut≥50% ) |
Spesifikasi teknikal dan data prestasi