| Parameter | Nilai |
|---|---|
| C2 | |
| Nota | 2011 |
| Jenis | Attachment plug |
| Kedalaman | 78 mm |
| Lebar | 63 mm |
| Ketinggian | ≤ 2000 m (amsl) |
| Jenis EN | T3 |
| Jenis produk | Device protection |
| Jenis pemasangan | Plugging into the mains socket |
| Arus yang dinilai | 1.5 A (25 °C) |
| Keluarga produk | MAINTRAB |
| Bilangan port | One |
| Bahan perumahan | PA 6 |
| Tahap pencemaran | 2 |
| Kaedah sambungan | RJ45 |
| Voltan nominal UN | 230/400 V AC (TN) |
| Lukisan dimensi | |
| Arah tindakan | L/N-PE & Signal Line-Earth Ground |
| Bahan penebat | PA 6 |
| Kapasiti (Teras-Teras) | typ. 6 nF |
| Gelombang gabungan UOC | 4 kV |
| Tahap perlindungan | IP20 (Child-proofing) |
| Frekuensi nominal fN | 50 Hz (60 Hz) |
| Kategori voltan lampau | III |
| IPE arus baki | ≤ 5 µA |
| Nilai CTI bahan | 400 |
| Kapasiti (Teras-Bumi) | typ. 5 pF |
| Arus beban dinilai IL | 16 A (30 °C) |
| Masa tindak balas tA(LN) | ≤ 25 ns |
| Masa tindak balas tA(L-PE) | ≤ 100 ns |
| Masa tindak balas tA(N-PE) | ≤ 100 ns |
| Pengelasan ujian IEC | C1 |
| Tingkah laku TOV di UT(LN) | 335 V AC (5 s / withstand mode) |
| Piawaian/spesifikasi | IEC 61643-11 |
| Tingkah laku TOV di UT(L-PE) | 440 V AC (5 s / withstand mode) |
| Tingkah laku TOV di UT(N-PE) | 1200 V AC (200 ms / safe failure mode) |
| Rintangan penebat Riso | ≥ 20 kΩ |
| Fius sandaran maksimum yang diperlukan | 16 A (gG / B / C) |
| Untuk kegunaan khusus negara dalam | D, A, NL, E, S, FIN, TR |
| Voltan ujian rujukan UREF | 255 V AC |
| Masa tindak balas tA (baris-baris) | ≤ 1 ns |
| Masa penetapan semula denyutan (garisan-garisan) | ≤ 1 ms |
| Masa tindak balas tA (garis-bumi) | ≤ 100 ns |
| Penggunaan kuasa siap sedia PC | ≤ 1 VA |
| Voltan berterusan maksimum UC | 6 V DC |
| Mesej kerosakan perlindungan lonjakan | optical |
| Suhu ambien (operasi) | -25 °C ... 75 °C |
| Voltan baki di Iamax, (PE) | ≤ 1 kV (at 1 kA) |
| Kelembapan yang dibenarkan (operasi) | 5 % ... 95 % |
| Voltan baki di Iamax, (LN) | ≤ 1 kV (at 1 kA) |
| Tahap perlindungan voltan Naik (LN) | ≤ 1.2 kV |
| Voltan baki di Iamax, (L-PE) | ≤ 1 kV (at 1 kA) |
| Tahap perlindungan voltan Naik (L-PE) | ≤ 1.5 kV |
| Tahap perlindungan voltan Naik (N-PE) | ≤ 1.5 kV |
| Penarafan arus litar pintas ISCCR | 1.5 kA AC |
| Fius sandaran maksimum dengan pendawaian cabang | 16 A (gG / B / C) |
| Arus berkesan operasi ICat UC | 500 µA |
| Penarafan mudah terbakar mengikut UL 94 | V-0 |
| Arus nyahcas nominal In(8/20) µs | 3 kA (> 5x) |
| Tahap perlindungan voltan Naik (talian-talian) | ≤ 65 V (C1 - 1 kV / 500 A) |
| Suhu ambien (penyimpanan/pengangkutan) | -25 °C ... 75 °C |
| Tahap perlindungan voltan Naik (line-earth) | ≤ 900 V (C2 - 4 kV / 2 kA) |
| Voltan baki pada In (konduktor-tanah) | ≤ 50 V |
| Jumlah arus nyahcas Itotal(8/20) µs | 10 kA |
| Voltan baki pada In(konduktor-konduktor) | ≤ 20 V |
| Voltan operasi berterusan maksimum UC(LN) | 275 V AC |
| Voltan operasi berterusan maksimum UC(L-PE) | 360 V AC |
| Voltan operasi berterusan maksimum UC(N-PE) | 360 V AC |
| Kapasiti bawaan arus ulang-alik (talian-talian) | 1 A - 1 s |
| Kapasiti daya tampung arus ulang-alik (garis-bumi) | 10 A - 1 s |
| Arus nyahcas nominal In(8/20) µs (garis-garis) | 650 A |
| Arus denyut nominal Ian (10/1000) µs (garis-garis) | 120 A |
| Frekuensi potong fg (3 dB), sim. dalam sistem 100 Ω | typ. 300 kHz |
| Arus nyahcas nominal In(8/20) µs (line-ground) | 2.5 kA |
| Arus denyut nominal Ian (10/1000) µs (garis-bumi) | 200 A |
| Had voltan output pada lonjakan 1 kV/µs (line-earth) | ≤ 900 V |
| Had voltan output pada 1 kV/µs (garisan-garisan) statik | ≤ 10 V |
| Had voltan output pada 1 kV/µs (line-earth) statik | ≤ 900 V |
Spesifikasi teknikal dan data prestasi