| Parameter | Nilai |
|---|---|
| GTIN | 4046356410229 |
| Nota | Made to Order (non-returnable) |
| Kunci Pesanan | 1586277 |
| Halaman katalog | Page 507 (C-2-2017) |
| Unit pembungkusan | 10 pc |
| Negara asal | DE (Germany) |
| Nombor tarif tersuai | 85366990 |
| (Data Komersial Utama) | The axial screw connection must be established using a 2 mm Allen key (for stranded conductors only) |
| Kuantiti pesanan minimum | 10 pc |
| Saiz (Data Komersial Utama) | D7 |
| (Piawaian dan Peraturan) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| (Ciri-ciri elektrik) | IEC 60352 |
| Arus yang dinilai (Data bahan) | 40 A |
| Sambungan (Data Komersial Utama) | Note regarding axial connection technology:Only for stranded wires. The specified conductor cross sections refer to the geometric cross section of the cable used.Cables with a geometric cross section which deviates significantly from the nominal cable cross section must be checked before use.The axial connection technology connection space is designed for fine strand cables according to VDE 0295 Class 5. Deviating cable structures (e.g., Class 6 cables) must be checked before use.Assembly instructionsBefore assembly, ensure that the tapered screw is fully loosened (chamber is open). Cables must not be twisted. The wires must be pushed into the contact chamber as far as they will go (until the insulation touches the contact). Hold the wires in position and tighten using an Allen key. The used wire end must be cut off before reconnection. The terminal screw must only be retightened once to prevent the litz wires from breaking. To prevent damage to the contact, the wire/cable must be mechanically held at an appropriate distance from the connection point (e.g., when used in a plate cut out). For notes on correct execution, see DIN VDE 0100-520:2003-06. Unused connections must be tightened with maximum torque. |
| Voltan lonjakan dinilai (Data bahan) | 6 kV |
| Berat setiap Keping (tidak termasuk pembungkusan) | 23.410 g |
| Bahan sentuhan (Keadaan ambien) | Copper alloy |
| Voltan yang dinilai (III/3) (Data bahan) | 400 V |
| RoHS (Piawaian dan Peraturan) China | Environmentally Friendly Use Period = 50 |
| REACh SVHC (Piawaian dan Peraturan) | Lead 7439-92-1 |
| Kaedah sambungan (Data Komersial Utama) | Axial screw connection |
| Penomboran kenalan (Data Komersial Utama) | 1 - 2 |
| Tork pengetatan (Data Komersial Utama) | 1.8 Nm |
| Suhu ambien (operasi) (Umum) | -40 °C ... 125 °C (including heating up of contacts) |
| Tahap pencemaran (Data Komersial Utama) | 3 |
| Bilangan jawatan (Data Komersial Utama) | 2+PE |
| Kategori voltan lampau (Data Komersial Utama) | III |
| Arahan pemasangan (Data Komersial Utama) | To ensure correct use, installation in housing with IP54 protection or better is required |
| Keratan rentas konduktor (Data Komersial Utama) | 4 mm² ... 10 mm² |
| Bahan pembawa sentuhan (Keadaan ambien) | PC |
| Bahan permukaan sentuh (Keadaan ambien) | Ag |
| Kitaran pemasukan/penarikan balik (Data Komersial Utama) | ≥ 500 |
| Keratan rentas sambungan AWG (Data Komersial Utama) | 10 ... 8 |
| Sambungan dalam akaun dengan standard (Ciri-ciri elektrik) | CUL |
| Panjang pelucutan wayar individu (Data Komersial Utama) | 8 mm +1 |
| Peraturan pembinaan dan pengujian (Ciri-ciri elektrik) | DIN VDE 0627/86 |
| Penarafan mudah terbakar mengikut UL 94 (Ciri-ciri elektrik) | V0 |
Spesifikasi teknikal dan data prestasi