| Parameter | Nilai |
|---|---|
| Transient protection; Suppressor diode | |
| Jenis | block modular |
| Kedalaman | 54 mm |
| Lebar | 35 mm |
| Ketinggian | 126.1 mm |
| Sijil | UL 20 ATEX 2441X |
| Nama keluaran | Analog outputs |
| Cabutan semasa | max. 150 mA |
| Format data | IB IL, S7-compatible |
| Jenis produk | I/O component |
| Jenis pemasangan | DIN rail mounting |
| Pengenalpastian | II 3 G Ex ec IIC T4 Gc |
| Keluarga produk | Axioline F |
| Voltan bekalan | 5 V DC (via bus base module) |
| Nama sambungan | Axioline F connector |
| Semakan artikel | 07 |
| Tahap pencemaran | 2 (IEC 60664-1, EN 60664-1) |
| Kelas perlindungan | III (IEC 61140, EN 61140, VDE 0140-1) |
| Panjang pelucutan | 8 mm |
| Kaedah sambungan | Bus base module |
| Kedudukan pemasangan | any (no temperature derating) |
| Bilangan output | 4 |
| Skop penghantaran | including bus base module and Axioline F connectors |
| Kawasan alamat input | 8 Byte |
| Nota tentang dimensi | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
| Litar pelindung | Short-circuit and overload protection; electronic |
| Hartanah istimewa | Extreme conditions version |
| Kelajuan penghantaran | 100 Mbps |
| Lukisan dimensi | |
| Nota mengenai permohonan | Only for industrial use |
| Kawasan alamat output | 8 Byte |
| Kemas kini data proses | 140 µs |
| Tahap perlindungan | IP20 |
| Bilangan antara muka | 2 |
| Kategori voltan lampau | II (IEC 60664-1, EN 60664-1) |
| Julat voltan bekalan | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Teknologi sambungan | 2-conductor |
| Isyarat keluaran semasa | 0 mA ... 20 mA |
| Isyarat keluaran voltan | 0 V ... 5 V |
| Rujukan kepada piawaian | EN IEC 60079-0, EN IEC 60079-7 |
| Data parameter yang diperlukan | 14 Byte |
| Tekanan udara (operasi) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Resolusi penukar D/A | 16 bit |
| Keratan rentas konduktor AWG | 24 ... 16 |
| Data konfigurasi yang diperlukan | 7 Byte |
| Keratan rentas konduktor tegar | 0.2 mm² ... 1.5 mm² |
| Nota tentang kaedah sambungan | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
| Keratan rentas konduktor, tegar | 0.2 mm² ... 1.5 mm² |
| Suhu ambien (operasi) | -25 °C ... 60 °C (Standard, applications with UL approval, use in zone 2 potentially explosive area) |
| Arus beban beban/output output | ≤ 500 Ω |
| Output voltan beban/output | ≥ 1 kΩ |
| Perwakilan nilai output | 16 bits (15 bits + sign) |
| Tekanan udara (penyimpanan/pengangkutan) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Keratan rentas konduktor fleksibel | 0.2 mm² ... 1.5 mm² |
| Kelembapan yang dibenarkan (operasi) | 5 % ... 95 % (non-condensing) |
| Keratan rentas konduktor, fleksibel | 0.2 mm² ... 1.5 mm² |
| Suhu ambien (penyimpanan/pengangkutan) | -40 °C ... 85 °C |
| Nota mengenai teknologi sambungan | shielded, twisted pair |
| Kelembapan yang dibenarkan (penyimpanan/pengangkutan) | 5 % ... 95 % (non-condensing) |
| Voltan ujian: output bekalan (I/O)/analog 24 V | 500 V AC, 50 Hz, 1 min. |
| Voltan ujian: Output analog/pembumian berfungsi | 500 V AC, 50 Hz, 1 min. |
| Pelesapan kuasa maksimum untuk keadaan nominal | 3.4 W |
| Voltan ujian: Bekalan 24 V (I/O) / pembumian berfungsi | 500 V AC, 50 Hz, 1 min. |
| Voltan ujian: Bekalan 5 V output bas tempatan (UBus)/analog | 500 V AC, 50 Hz, 1 min. |
| Voltan ujian: Bekalan 5 V bas tempatan (UBus) / pembumian berfungsi | 500 V AC, 50 Hz, 1 min. |
| Voltan ujian: Bekalan 5 V bas tempatan (UBus) / Bekalan 24 V (I/O) | 500 V AC, 50 Hz, 1 min. |
Spesifikasi teknikal dan data prestasi
Panduan pemasangan dan operasi